An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Watson TomlinsonIndustry Specialist, NuclearFlowserve Corp. OPPD-Fort Calhoun CCW Pump Testing 8X18 SE

  2. Fort Calhoun Station utilizes qty. (3) IR 8X18SE (Flowserve heritage) CCW pumps. The CCW pumps appeared to have been operated beyond their original manufacturer pump curves without proper justification and analysis. The testing was performed to determine exactly where the pumps were operating relative to the original head-capacity curve, at different system demands. • OEM Pump Data: • Make: Flowserve/Ingersoll-Rand • Model: 8X18 SE • Number Stages: 1 • Style: Horizontally split volute type • Driver: Motor [250 hp] • Design Head: 210 ft • Design Flow: 3425 gpm • Design Speed: 1750 rpm

  3. CCW 3B Pump Test Performance Comparison between the October and June Test