3442 Industrial Instruments 2 Chapter 9 Controller Principles

Princess Sumaya Univ. Electronic Engineering Dept. 3442 Industrial Instruments 2 Chapter 9 Controller Principles. Dr. Bassam Kahhaleh. 9: Controller Principles. Process Characteristics Process Equation A process-control loop regulates some dynamic variable in a process. Example :

vanig
Download Presentation

3442 Industrial Instruments 2 Chapter 9 Controller Principles

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Princess Sumaya Univ.Electronic Engineering Dept. 3442Industrial Instruments 2Chapter 9Controller Principles Dr. Bassam Kahhaleh

  2. 3442 - Industrial Instruments 2 9: Controller Principles Process Characteristics • Process Equation A process-control loop regulates some dynamicvariable in a process. Example: The control of liquid temperature in a tank. The controlled variable is the liquid temperature TL TL is a function: TL = F(QA, QB, QS, TA, TS, TO)

  3. 3442 - Industrial Instruments 2 9: Controller Principles Process Characteristics • Process Load • Identify a set of values for the process parameters that results in the controlledvariable having the setpoint value. • This set = nominalset. Process load = all parameter set – the controlledvariable

  4. 3442 - Industrial Instruments 2 9: Controller Principles Process Characteristics • Process Change • Process Load Change A parameter changes value from its nominal value causes the controlled value to change from its setpoint. • Transient Change A temporary change of a parameter value.

  5. 3442 - Industrial Instruments 2 9: Controller Principles Process Characteristics • Process Lag The time it takes for the process to respond after a process load or transient change occurs, to ensure that the controlled variable returns to the setpoint.

  6. 3442 - Industrial Instruments 2 9: Controller Principles Process Characteristics • Self Regulation The tendency of some processes to adopt a specific value of the controlled variable for nominal load with no control operations.

  7. 3442 - Industrial Instruments 2 9: Controller Principles Control System Parameters • Error e = r – b. • Percentage

  8. 3442 - Industrial Instruments 2 9: Controller Principles p: percentage Control System Parameters • Error • Control Parameter u: actual

  9. Speed (RPM) 600 140 I (mA) 4 20 3442 - Industrial Instruments 2 9: Controller Principles Example A controller outputs a 4 – 20 mA signal to control motor speed from 140 – 600 RPM with a linear dependence. Calculate: Control System Parameters • Current corresponding to 310 RPM • The value of (a) in percent. 310

  10. Speed (RPM) 600 310 140 I (mA) 4 20 3442 - Industrial Instruments 2 9: Controller Principles Example Sp = m I + So 140 = 4 m + So 600 = 20 m + So  m = 28.75 rpm/mA So = 25 rpm 310 = 28.75 I + 25  I = 9.91 mA Control System Parameters

  11. 3442 - Industrial Instruments 2 9: Controller Principles Control System Parameters • Control Lag The time it takes for the final control element to adopt a new value (as required by the process-control loop output) in response to a sudden change in the controlled variable. • Dead Time The elapsed time between the instant a deviation (error) occurs and when the corrective action first occurs. • Cycling The cycling of the variable above and below the setpoint value.

  12. 3442 - Industrial Instruments 2 9: Controller Principles Control System Parameters • Controller Modes • Continuous / Discontinuous Smooth variation of the control parameter versus ON / OFF. • Reverse / Direct Action An increasing value of the controlled variable causes an decreasing / increasing value of the controller output.

  13. 3442 - Industrial Instruments 2 9: Controller Principles Discontinuous Controller Modes • Two-Position Mode Neutral Zone

  14. 3442 - Industrial Instruments 2 9: Controller Principles Discontinuous Controller Modes • Two-Position Mode Example A liquid-level control system linearly converts a displacement of 2 – 3 m into a 4 – 20 mA control signal. A relay serves as the two-position controller to open or close an inlet valve. The relay closes at 12 mA and opens at 10 mA. Find: The relation between displacement level and current The neutral zone

  15. I (mA) 20 4 2 3 Displacement (m) 3442 - Industrial Instruments 2 9: Controller Principles Discontinuous Controller Modes • Two-Position Mode Example H = K I + HO 2 = K (4) + HO 3 = K (20) + HO  K = 0.0625 m / mA HO = 1.75 m HH = 0.0625 * 12 + 1.75 = 2.5 m HL = 0.0625 * 10 + 1.75 = 2.375 The neutral zone = HH – HL = 2.5 – 2.375 = 0.125 m

  16. 3442 - Industrial Instruments 2 9: Controller Principles Discontinuous Controller Modes • Two-Position Mode Example As a water tank loses heat, the temperature drops by 2 K per minute. When a heater is on, the system gains temperature at 4 K per minute. A two-position controller has a 0.5 min control lag and a neutral zone of ± 4 % of the setpoint about a setpoint of 323 K. Plot the tank temperature versus time.

  17. 3442 - Industrial Instruments 2 9: Controller Principles Discontinuous Controller Modes • Two-Position Mode Example Neutral zone = 310 – 336 K Temp. gain = 4 K per minute Setpoint = 323 K Temp. loss = 2 K per minute Control lag = ½ minute

  18. 3442 - Industrial Instruments 2 9: Controller Principles Discontinuous Controller Modes • Multiposition Mode

  19. 3442 - Industrial Instruments 2 9: Controller Principles Discontinuous Controller Modes • Multiposition Mode Example

  20. 3442 - Industrial Instruments 2 9: Controller Principles Discontinuous Controller Modes • Floating-Control Mode If the error is zero, the output does not change but remains (floats) at whatever setting it was when the error went to zero.

  21. 3442 - Industrial Instruments 2 9: Controller Principles Discontinuous Controller Modes • Floating-Control Mode • Single Speed

  22. 3442 - Industrial Instruments 2 9: Controller Principles Discontinuous Controller Modes • Floating-Control Mode • Single Speed

  23. 3442 - Industrial Instruments 2 9: Controller Principles Discontinuous Controller Modes • Floating-Control Mode Example Suppose a process error lies within the neutral zone with p = 25%. At t = 0, the error falls below the neutral zone. If K = +2% per second, find the time when the output saturates. Solution 100 % = (2 %/s * t) + 25 % t = 37.5 s

  24. 3442 - Industrial Instruments 2 9: Controller Principles Discontinuous Controller Modes • Floating-Control Mode • Multispeed

  25. 3442 - Industrial Instruments 2 9: Controller Principles Continuous Controller Modes • Proportional Control Mode Direct (- K) & Reverse (+ K) Action

  26. 3442 - Industrial Instruments 2 9: Controller Principles Continuous Controller Modes • Proportional Control Mode % per % Proportional Band:

  27. 3442 - Industrial Instruments 2 9: Controller Principles Continuous Controller Modes • Proportional Control Mode Example Valve A: 10 m3/h per percent. PO = 50 % KP = 10 % per % Valve B changes from 500 m3/h to 600 m3/h Calculate: The new controller output The new offset error

  28. 3442 - Industrial Instruments 2 9: Controller Principles Continuous Controller Modes • Proportional Control Mode Solution QA must go up to 600 m3/h QA = 10 m3/h * P P = 60 % 60 = 10 eP + 50 eP = 1 % Example Valve A: 10 m3/h per percent. PO = 50 % KP = 10 % per % Valve B changes from 500 m3/h to 600 m3/h Calculate: The new controller output The new offset error

  29. 3442 - Industrial Instruments 2 9: Controller Principles Continuous Controller Modes • Integral Control Mode Integral Time: TI = 1 / KI % per sec % sec

  30. 3442 - Industrial Instruments 2 9: Controller Principles Continuous Controller Modes • Integral Control Mode Example An integral controller is used for speed control with a setpoint of 12 rpm within a range of 10 – 15 rpm. The controller output is 22% initially. The constant KI = - 0.15 % per second per % error. If the speed jumps to 13.5 rpm, calculate the controller output after 2 s for a constant ep.

  31. 3442 - Industrial Instruments 2 9: Controller Principles Continuous Controller Modes • Integral Control Mode Example setpoint = 12 rpm (range of 10 – 15 rpm) P(O) = 22% KI = – 0.15 speed = 13.5 rpm constant ep 2 seconds time Solution eP = (12–13.5)/(15–10)*100 %. eP = – 30 % P(t) = KIeP t + P(0) P(t) = (– 0.15) * (– 30) * 2 + 22 P = 31 %

  32. 3442 - Industrial Instruments 2 9: Controller Principles Continuous Controller Modes • Derivative Control Mode Not used alone because it provides no output when the error is constant. sec

  33. 3442 - Industrial Instruments 2 9: Controller Principles Continuous Controller Modes • Derivative Control Mode Example

  34. 3442 - Industrial Instruments 2 9: Controller Principles Composite Control Modes • Proportional – Integral Control (PI)

  35. 3442 - Industrial Instruments 2 9: Controller Principles Composite Control Modes • PI Example KP = 5 KI = 1 sec-1 P(0) = 20% Plot a graph of the controller output as a function of time

  36. 3442 - Industrial Instruments 2 9: Controller Principles Composite Control Modes • PI Example KP = 5 KI = 1 sec-1 P(0) = 20%

  37. 3442 - Industrial Instruments 2 9: Controller Principles Composite Control Modes • Proportional – Derivative Control (PD)

  38. 3442 - Industrial Instruments 2 9: Controller Principles Composite Control Modes • PD Example KP = 5 KD = 0.5 sec Po = 20%

  39. 3442 - Industrial Instruments 2 9: Controller Principles Composite Control Modes • Three – Mode Controller (PID)

  40. 3442 - Industrial Instruments 2 9: Controller Principles End of Chapter 9