B-field sensitive components TB 23.2.04 L.Jirden

B-field sensitive components TB 23.2.04 L.Jirden. Estimated B-fields in UX B-field tests done Sensitive components in UX Summary. B-field in UX – worst case (D.Swoboda TB 27.1.04). Rack group A and B: ~ 110 Gauss. Rack group D: ~ 200 Gauss.

gil
Download Presentation

B-field sensitive components TB 23.2.04 L.Jirden

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. B-field sensitive componentsTB 23.2.04 L.Jirden • Estimated B-fields in UX • B-field tests done • Sensitive components in UX • Summary

  2. B-field in UX – worst case (D.Swoboda TB 27.1.04) Rack group A and B: ~ 110 Gauss Rack group D: ~ 200 Gauss

  3. B-field in UX – worst case (D.Swoboda TB 27.1.04) Rack group C: ~ 50 Gauss

  4. B-field tests • Very few tests done so far • Power supplies (B.Allongue, ESS group): • Standard Wiener PL500 - non-shielded • Wiener Marathon PS – shielded (under development) • VME fan-tray (B.Allongue, ESS group) • Ethernet (T.Krawutschke, KIP, Heidelberg) • Transceivers

  5. Fan restarts Fan stops B-field tests: PL500 • Power module fan: • PAPST 614MN • This fan is used to cool the single power modules type MEH

  6. Fan restarts Fan stops B-field tests: PL500 • Power module fan: • NMB 1606 KL • This fan is used to cool the double power modules type MDL.

  7. B-field tests: PL500

  8. B-field tests: Marathon • Shielded power modules:

  9. B-field tests: Marathon

  10. B-field tests • VME fan tray • Behaves similar to PAPST 614MN: max 80 Gauss tolerated • Ethernet transceiver • Vacor PT4153S transformer chip tested • Operation depends on orientation; in worst direction all traffic stops at: ~200-220 Gauss

  11. Which devices are sensitive to B-field? • Any device containing • Ventilators • Transformers • Filters • Relays

  12. Sensitive components in UX

  13. Sensitive components in UX

  14. Summary • Refine B-map - make more stray field measurements • –At critical rack locations, outside/inside racks • Plan rack layouts in view of water cooling only (racks without ventilator units) • Test • Alternative fans, fans inside power box, CAEN, AREM Pro, PLC’s, Ethernet, pulser equipment, laser equipment, etc. • Move sensitive equipment to less exposed racks wherever possible • Other devices? - input from all detectors required!