200 likes | 211 Views
Learn about Delta, Wye, Delta-to-Wye, Wye-to-Delta Connections, Voltage Polarity, and more in 3-phase circuits. Understand how to configure transformers for efficient power distribution.
E N D
Chapter 4Transformer Connections Voltage Transformation · Three-Phase Circuits · Delta Connections · Wye Connections · Delta-to-Wye Connections · Wye-to-Wye Connections · Wye-to-Delta Connections · Delta-to-Delta Connections · Open Delta Connections · Delta Connection with High Leg to Ground · Three-Phase Transformer Polarity
The low‑voltage winding of a standard distribution transformer connected to a single-phase circuit is normally made with two equal coils. These sections are arranged so that they may be connected in series or parallel.
The polarity of a transformer may be determined using a known transformer or with AC voltage.
A delta connection has the wires from the ends of each coil connected end-to-end to form a closed loop.
Studying the current in a delta-connected system at both 0° and 90° illustrates the current flow in a delta-connected system.
A wye connection has one end of each coil connected together and the other end of each coil left open for external connections.
Studying the current in a wye-connected system at both 0° and 90° illustrates the current flow in a wye-connected system.
A 3-phase delta-to-wye connection is often used for distribution where a four-wire secondary distribution circuit is required.
Three single-phase transformers may be connected in a wye-to-wye connection to form a 3-phase transformer.
A wye-to-delta connection permits single-phase and 3-phase loads to be drawn simultaneously from the delta-connected secondary at the same voltage.
In a wye-to-delta connection of three single-phase transformers, one unit may be disconnected from the circuit and service maintained with the secondary operating in open delta connection at 57.7% of normal bank capacity.
In a delta-to-delta connection, the voltage of each transformer is equal to the 3-phase line voltage and the current in each of the transformers is only 57.7% of the line current.
Grounding one of the midpoints of the windings provides 240 V/120 V, single-phase, 3-wire service for lighting applications.
An open delta connection makes 3-phase power available anywhere along the distribution line with the use of only two transformers rather than the usual three.
A delta connection with a high leg to ground provides 240 V, 3-phase power to equipment and 120 V power for lighting and receptacles.
The phase sequence on the secondary of a three-phase transformer is the same as the phase sequence on the primary.
Transformers are classified into connection groups according to their phase shift.