1 / 9

Transient Surges and Surge Suppression Technologies

Transient Surges and Surge Suppression Technologies. Joe Kenney International Business Development Manager Caribbean, Latin America and Asia Pacific. Outside & Inside Causes of Transients. Outside Causes Environmental i.e. Lightning Power Company i.e. Grid Switching Other Users

lucio
Download Presentation

Transient Surges and Surge Suppression Technologies

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Transient Surges and Surge Suppression Technologies Joe Kenney International Business Development Manager Caribbean, Latin America and Asia Pacific

  2. Outside & InsideCauses of Transients • Outside Causes • Environmental • i.e. Lightning • Power Company • i.e. Grid Switching • Other Users • Power Quality Decreases as the Number of Other Users Sharing the Power Feed Increases • Inside Causes • Internal Power Switching • i.e. Air Conditioning, Refrigeration Systems, Florescent Light Ballasts, Elevators, Co-pay Machines to Coffee Pots, Various Types of Motor Starter Contactors

  3. All Suppressors Should Be Tested with Both Long Waveforms (10/1000 µs) and Short Waveforms (8/20 µs) AC switching transients (10/1000 µs) occur more often than lightning (8/20 µs). The suppressor will need to dissipate 50 times more energy in the real world (10/1000 µs) than it will with the 8/20 µs waveform test. Why?

  4. IP Represents amperage diverted by the SPD in a 8/20 surge 3000 8/20 µsec (shortwave) Represents amperage diverted by the SPD in a 10/1000 surge 10/1000 µsec (longwave) 2500 2000 The SPD will dissipate approximately 50 times more power with the 10/1000 than the 8/20 waveform test Current (I) 1500 1000 500 0 10 100 200 300 400 500 600 700 800 1000 Time (µs) Test Current Waveforms Comparison (Per IEEE C62.41-1991)

  5. Requirements for a Surge Protective Device (SPD) • Response Time • Voltage Protection Level • Surge Current • Power Dissipation • Disturbance Free Operation • Performance Reliability • Operating Life • Lead Length

  6. 500 Failure Level 400 Degradation, Errors & Possible Damage Level Voltage 300 Protection Level 200 170 0 Time (ms) Voltage Protection LevelFor 120 VAC Nominal (L-N)(100 to 132 VAC)

  7. 600 Higher voltage limiting suppressor must dissipate the power in area 1 Lower voltage limiting suppressor must dissipate the power in areas 1 & 2 400 Voltage 300 120 0 Time (ms) Power Dissipation ComparisonFor 120 VAC Nominal (L-N)(100 to 132 VAC)

  8. Filter MOV Gas Tube *SASD No No Degrade w/use No > 130% No No Degrade w/use No >130% Yes Yes Long No Frequency Dependant Yes Yes Long Yes <130% Technology Comparison Non Degrading Response Time <5ns Expected Life Reliable Performance Voltage Protection Level * SASD results based on Lattice Matrix or ASAT design technology

  9. Eliminating transient overvoltages: reduces operation costs reduces downtime, repair & maintenance costs A surge suppressor is not an insurance policy, rather an assurance that your system won’t have problems. Insurance policies cover repair costs after failure, not losses related to downtime which can far exceed repair costs. By evaluating overall system cost & investment, it’s clear that transient overvoltage suppression equipment must become an integral part of any electronic system. Conclusion

More Related