An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. NeSSI-II Network and Sensor Developments Networked Sampling System (NeSSI-Generation II) Development and Field Test by John Mosher, Bob Nickels – Honeywell Sensing & Control and Ulrich Bonne – Honeywell Laboratories

  2. NeSSI-II Network and Sensor Developments • Outline: • Project Team • Definition and NeSSI functions. Status of NeSSI-I • Challenges for NeSSI-II components: • Networked Components • Easy plug-and-play • Intrinsically Safe • Reliable • Affordable • Demo and field test of NeSSI-II • Sensor Developments

  3. NeSSI-II Network and Sensor Developments • NeSSI Generation II • Being Developed by a • Supplier Team • Supplier Team: • Steve Doe (256) 435-2130 Parker-Hannifin • Dave Simko (440) 349-5934 Swagelok • Richard Hughes (310) 515-2866 Autoflow • Bob Nickels (815) 235-5735 Honeywell-ACS • John Mosher (209) 330-4004 Honeywell-ACS • Ulrich Bonne (763) 954-2758 Honeywell Labs

  4. NeSSI-II Network and Sensor Developments • User Team for Potential DoE NeSSI Project • Peter van Vuuren (281) 834-2988 ExxonMobil • Rob DuBois (780) 998-5630 Dow • Joe Andrisani (302) 695-3156 DuPont • Steve Wright (423) 229-4060 Eastman • Bob Reed (215) 652-1691 Merck • Paul Vahey (973) 455-5977 Honeywell-SM • Don Young/Don Nettles (510) 242-3298 ChevronTexaco • Frank Schweighardt (610-481-6683) Air Products • George Vickers (630) 420-3701 BP • Paul Barnard (713) 336-5351 EquistarChemicals • Steve Doherty (847) 982-7465 Pharmacia • Carol Zrybko Kraft • Michelle Cohn UOP • Alan Eastman/Randy Heald (918) 661-3475 ConocoPhillips • Center for Process Analytical Chemistry (CPAC) • Mel Koch (206) 616-4869 U.Washington, CPAC

  5. NeSSI Benefits |------------------------------------+------------------------------------| | Now | NeSSI | |------------------------------------+------------------------------------| | Analyzer houses | Analyzer cabinets close to sample | | | point | |------------------------------------+------------------------------------| | Long heat traced lines | Short heat traced lines | |------------------------------------+------------------------------------| | Extensive design to bring sample | Minimal Design | | to sensor | | |------------------------------------+------------------------------------| | One at a time assembly | Modular "tinker-toy" type assembly| |------------------------------------+------------------------------------| | Field repair | Modular replacement of components | | | or systems, repair in shop or at | | | vendors | |------------------------------------+------------------------------------| | Sample may not reach analyzer | Sample flow is validated | |------------------------------------+------------------------------------| Compliments of Bruce Johnson, DuPont

  6. Fig. 1. Functions of a Process Sampling System. Courtesy of ExxonMobil

  7. Fig. 1a. Traditional Stream Sampling System in a Petrochemical Plant. No Modular or Standardized Components Courtesy of P.vanVuuren, ExxonMobil

  8. NeSSI Generation I Fig. 3. Sampling System for Measurement of H2O and O2 ppm in a High-Purity Hydrocarbon Stream. Miniaturized Version Courtesy of D.Simko, Swagelok

  9. NeSSI Generation II What is Generation II? NeSSI II = SP76 + IS + CAN + SAM SP76 = NeSSI Generation I from SEMI IS = Intrinsic Safety CAN = Controller Area Network – DeviceNet SAM = Sensor Actuator Manager – Open Interface to Plant-wide Network and/or Analyzer Reliable, Networked, Modular, Safe, Open, and Affordable!

  10. NeSSI Generation II IS NeSSI II = SP76 + IS + CAN + SAM CAN SAM SP76

  11. NeSSI Generation II • PROJECT ABSTRACT • The Problem: Need for a networked, standardized, int.safe, modular, affordable and reliable process stream sampling and sensor system. Sampling systems now are causes for down-time and questionable process stream samples followed by costly control errors. • Objectives are to: •  Accelerate development of the prototype system component • such as intrinsically safe, digital pressure, temperature and • flow (p, T, F), sensors, smart valves, flow-controllers, and a • sensor/actuator networking capability •  Build, demonstrate, and test 1-2 NeSSI-II units, and •  Provide a platform for incorporating analytical sensors right • into the sampling system.

  12. ABSTRACT (cont’d.) Benefits Enabled by Full NeSSI Implementation:  Reduce down time, energy use & operating & sampling cost: U.S.: 0.1-0.2 Q/y or $10-20 billion  Bring these savings to the end-users at an earlier date, and  Reduce the business risk to the Supplier and End-User End-Users are members from across the processing industries: chemical, petrochemical, power generation, refining, food, beverage and dairy, pulp & paper Schedule:  One year for design, build and lab-test  One year for installation and field testing Deliverables:  Interim and Final Reports (no hardware) on design of sensor hard- and software, NeSSI test results, benefits and recommendations Management of the Program: Honeywell + Consortium

  13. Table 1. NeSSI Generation I versus II From Rob Dubois, Dow, May’02

  14. Diagram of NeSSI-Gen2-POCA (Proof of Concept Assembly) to Check Networking and Control of Flow, Pressure and Temperature. (Courtesy of R.DuBois, DowChemical)

  15. Comparison of NeSSI Generation Designs Feature Generation I Generation II Generation III Signal Type 4-20 mA; discrete Serial bus Serial bus Wireless; Opt.Fiber Protection Purging, X-proof Low-Power IS Low-Power IS Enclos.Classif. Div.2(Seldom Flam.) Div.1(Often Flam.) Div.1 (Often Flam.) Sensor Locat’n Off-Substrate On-Substrate Mini-Substrate Analyzer Locat Off-Substrate On/Off-Substr. MicroAnalytical Intelligence Limited Processor OB Processor OB Ctrol.Philosophy Centralized Distrib’d (SAM) Distributed (SAM) Regulat’g Comp. Self-Contained On-Substr.w/PID On-Substr. w/PID Passive Comp. Pure Mechanical Electro-Mechan. Int. Electro-Mechan. Valves Manual or Pneum., Off On-Substr.Combi On-Substr.Combi Heating External Substr.-Integrated Substr.-Integrated Wiring Pwr/Sig X-proof conduit/cable IS Plug & Play IS Plug & Play Communication Individual Hard-Wired Networked Networked Cost High Moderate Moderate to low.

  16. ISO OSI 7-Layer Model Application Layer Presentation Layer Session Layer Transport Layer Network Layer Data Link Layer Physical Layer CAN Communications - Issues and Background • Issues/Questions: • 1. Is it feasible to embed all required device electronics, • microcontroller, and CAN communications into a NeSSI • SP-76 1.5 x 1.5” footprint? • 2. Is a CAN network capable of operating through an IS barrier? • Selection of CAN as a communications enabler for NeSSI • High Level Protocol • SDS, DeviceNet, CANOpen - all publicly available & proven • Data Link Layer • Master/slave, peer-to-peer, multicast messaging • All data types supported • Diagnostics • Carrier Sense Multiple Access with Collision Resolution • 16-bit CRC error checking, intell.network mgmt.capability • Physical Layer • Trunkline/multidrop with branches • Separate twisted pairs for signal and device power distribution • Up to 64 nodes, up to 500 meters trunk length • Intrinsic Safety

  17. Adaptation of Honeywell Temperature, Pressure, & Flow Sensors to NeSSI design standards. • Microbridge flow sensor interfaced to a typical miniature CAN microcontroller and 12 mm connector. • A similar interfacing • approach will be used in this project to connect existing sensors and actuators to • the CAN network. 12 mm by Bob Nickels, Honeywell

  18. CAN Communication - Feasibility and Intrinsic Safety Evaluation • DESCRIPTION OF TESTING: • Lab tests utilized SDS protocol and devices • A standard Zener Intrinsic Safety Barrier was used in series with both CAN communication signals. Component values were varied down to 4.3 volt Zeners and up to 100 ohms of series current-limiting resistance • 20 CAN devices were connected over trunk lines varying from 5 to 250 meters • Devices were configured to generate bus traffic as high as 20% bandwidth utilization to simulate worst-case conditions. • A CAN network analyzer was connected to monitor traffic and detect errors • TEST RESULTS: • After over 72 hours of operation, a total of 87 million messages had been sent with only two CAN error frames. This is well within normal expectations for a CAN bus. • CONCLUSION: (tentative) • It appears that industrial CAN networks are entirely suitable for applications such as NeSSI when used with a properly-designed IS barrier.

  19. Adaptation of Honeywell S1 Series Pressure Sensor to NeSSI design standards. • Current Status: • Sensor Design and SP76 housing qualified • Intrinsically Safe (IS). • CAN controller and transceiver chipsets • identified. • DeviceNet protocol selected and pretested • in selected chipset. • Preliminary CAN IS mode testing done. • First POCA units being built for February • delivery to Dow and ExxonMobil. • Next Steps: • Design and build PCBs incorporating selected sensing and communication chipsets/circuits. • Design and build PCBs into SP76 Housings and qualify full product as IS. • Establish and incorporate DeviceNet connector architecture for NeSSI applications. • Test Assemblies in full DeviceNet network. • Identify DeviceNet IS network restrictions and rules. • Propose establishment of DeviceNet IS Special Interest Group (SIG) to • ODVA (Open DeviceNet Vendors Association).

  20. Preliminary Investigation of SAM Controller Choices. •  MKS Instruments RMUd: • DeviceNet in/Ethernet out • 4” x 4” x 2” • USB and Serial Ports • 32 bit RISC Power PC Processor • 2-16MB ROM, 32-64MB SDRAM • Linux OS w/ JavaVirtual Machine • HMI Development Software Included • AutomationDirect 205:  • DeviceNet in/Ethernet out • 3” x 4” x 6” • Expandable local I/O, Serial Ports • Windows CE OS • Flowchart Programming • Visio HMI/Control Software

  21. NeSSI-II Sensor Developments… Cont’d • Compatibility with SP76 Footprint: • Pressure and Temperature • Flow (Gases and Liquids) • Self-Normalizing Flow Sensor • Thermal Conductivity for Process Monitoring • PHASED MicroAnalyzer

  22. Thermal Microbridge Flow Sensors for NeSSI-II

  23. Thermal Microbridge Flow Sensors for NeSSI-II

  24. Smart, IS, Miniature, p, T, F Sensors for NeSSI Adaptation.(Courtesy of Honeywell) Smart, T-Compens. TC Sensor Smart, T-Compens. Flow Sensor

  25. PHASED, a GC MicroAnalyzer

  26. Cross section of PHASED structure Multi-Stage Pre-concentration Side Views of PHASED structure and Operation Multi-stage release of analyte increases its concentration: ~100-fold with 1st stage ~100 x n-fold after n stages To Separator

  27. NeSSI Benefits, Nominal Ethylene Plant • Output: 1-2 billion pounds ethylene / year. • Savings enabled by smart, modular sampling (NeSSI I-III): • 430$k/y due to building and ownership cost savings, over 15 year life, of 2.4 and 4$M, respectively (per P.VanVuuren et al) • 100K$/y to 2+M$/y plant operational savings, due to conservative assumption of only a 1% improvement in process control (afford more measurements, and achieve greater efficiencies, less waste and less down time) • Significance: • 1-2% total savings by processing industries • Total US energy use & GDP: 1017 Btu/year & $1013/year • Assume US Process Industry uses 10% of total • NeSSI: 1-2% of 1016 Btu/y (0.1-0.2 quads/y) or $10-20B/y.

  28. NeSSI-II Network and Sensor Developments • CONCLUSIONS • Loaded CAN bus network error rate of 2: 87,000,000 is smaller than expected • Sensors compatible with NeSSI-II are around the corner: PT, FT, • IS certifications of P, F sensors were obtained before and need to be renewed • NeSSI-compatible microanalyzers are under development • Energy and cost savings are projected to be significant: 10-20 B$/y after NeSSI saturation of all industrial processes • Team approach enhances risk of success

  29. Acronyms CAN Controller Area Network ConnI Connectivity Initiative CPAC Center for Process Analytical Chemistry DoE-OIT Department of Energy, Office of Industrial Technologies EDS Electronic Data Sheet F Flow GC Gas chromatography GUI Graphical User Interface HMI Human-Machine Interface IFPAC International Forum for Process Analytical Chemistry IR Infra-red IS Intrinsically safe NeSSI New Sampling/Sensor Initiative NRE Non-Recurring Engineering labor ODVA Open DeviceNet Vendors Association OLE Object Linking and Embedding OPC OLE for Process Control based on Microsoft's OLE/COM technology OSI Open System Interconnect p Pressure PC Personal computer PDA Personal Digital Assistant SAM Sensor-Actuator Manager SDS Smart Distributed System SIG Special Interest Group T Temperature TEDS Transducer Electronic Data Sheet V Valve

  30. NeSSI-II Network and Sensor Developments • Thank You! • Contact Information: • John Mosher (209) 330-4004 Honeywell ACS • Bob Nickels (815) 235-5735 Honeywell ACS • Ulrich Bonne (763) 954-2758 Honeywell Labs