An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. ITS Ultra-Low-Mass Cooling System Enrico DA RIVA Manuel GOMEZ MARZOA WG4 Meeting - 10th April 2013 • D16 Prototype: • C4F10 thermal test results WG4 Meeting - 10th April 2013

  2. Experimental test upgrades • 6 NTCs over prototype. • Estimation of the power to room air. • New configuration of the C4F10 loop: • Full control of the refrigerant thermodynamic properties. • Full uncertainty analysis done. WG4 Meeting - 10th April 2013

  3. D16 prototype: C4F10 tests • No-Flow tests: • Power dissipated/absorbed to/from to room air • Agreement T sensors • Single-phase flow tests: • Pressure drop • Energy balance • General uncertainty • Two-Phase flow tests: • Thermal performance • Two-phase pressure drop • Compare with correlations D16 prototype summary. WG4 Meeting - 10th April 2013

  4. D16: No-Flow tests Procedure: Apply low power and record the average stave temperature. Correlate power dissipated to air vs. average stave temperature. When cooling the stave with full power, the power dissipated/absorbed to/from air can be estimated. WG4 Meeting - 10th April 2013

  5. D16: C4F10Single-phase tests Procedure: Apply low power densities (0.1 W cm-2). Ensure subcooled liquid everywhere. Check pressure drop and stave temperature. WG4 Meeting - 10th April 2013

  6. D16: C4F10Single-Phase tests Stave picks heat from room air WG4 Meeting - 10th April 2013

  7. D16: C4F10Two-phase tests WG4 Meeting - 10th April 2013

  8. Comparison: D12-D13-D16 K13D2U, 1.45mm ID K13D2U, 1.45mm ID squeezed WG4 Meeting - 10th April 2013

  9. D16: C4F10Two-phase tests Error in ΔT: ±1.5 K !! WG4 Meeting - 10th April 2013

  10. D16: C4F10Two-phase tests Error in ΔT: ±1.5 K !! WG4 Meeting - 10th April 2013

  11. D16: Thermographicpictures OUTLET INLET BEND WG4 Meeting - 10th April 2013

  12. D16: Thermographicpictures WG4 Meeting - 10th April 2013

  13. ITS Ultra-Low-Mass Cooling System Enrico DA RIVA Manuel GOMEZ MARZOA WG4 Meeting - 10th April 2013 • D16 Prototype: • C4F10 thermal test results WG4 Meeting - 10th April 2013

  14. D16: C4F10Two-phase tests WG4 Meeting - 10th April 2013